Question 4 (1 point)
A level process, shown above, has a valve operating range of \( 0-150 \mathrm{gpm} \) and the average ou???????

Question 4 (1 point) A level process, shown above, has a valve operating range of \( 0-150 \mathrm{gpm} \) and the average outflow (load) is \( 52 \mathrm{gpm} \). The valve is air-to-open (N.C). The level transmitter range is 0-950 inches, controller gain is \( 1.1 \), setpoint is 730 inches and the actual tank level is 700 inches. Determine the controller output percentage? \[ m=\quad \% \] Your Answer: Answer


We have an Answer from Expert

View Expert Answer

Expert Answer


It is a Reverse acting Gain controller where the output is defined as The tank level