(Solved): Problem 5 The cross section of a short axially loaded tied column shown below is reinforced with 8 ...



Problem 5
The cross section of a short axially loaded tied column shown below is reinforced with 8020 steel bars, the
concret

Problem 5 The cross section of a short axially loaded tied column shown below is reinforced with 8020 steel bars, the concrete compressive strength f' = 28 MPa, and yield strength of steel is fy = 420 MPa, calculate the following: Assume the clear cover is 40 mm. 400 mm Ø10@200 mm 8020 Required Answer Unit The provided reinforcement ratio (Pg) Does the reinforcement ratio satisfy the ACI code requirements? (Yes/No), why? The clear distance between steel bars (Sc) Does the clear distance between steel bars satisfy the ACI code requirements? (Yes/No), why? Does the provided spacing between ties satisfy the ACI code requirements? (Yes/No), why? The design load capacity (Pn) 400 mm


We have an Answer from Expert

View Expert Answer

Expert Answer


Solution. Does the provided reinforcement ratio satisfy the ACI standards? Yes. The provided reinforcement ratio satisfies the ACI 318-19 standard for the minimum and maximum reinforcement requirement for a non-prestressed column. As per section 10.6