(Solved): NEC 2017why do they provide ohms to neutral per 1000ft?  why not just say ohms per 1000ft? Tabl ...



NEC 2017

why do they provide ohms to neutral per 1000ft?  why not just say ohms per 1000ft?

Table 4 Alteraating Current Resistance and Reactance for 600-Volt Cables, 3-Phase, \( 60 \mathrm{H}^{-} \mathrm{H}, 75^{\circ
Table 4 Alteraating Current Resistance and Reactance for 600-Volt Cables, 3-Phase, \( 60 \mathrm{H}^{-} \mathrm{H}, 75^{\circ} \mathrm{C}\left(\mathrm{I} 67^{\circ} \mathrm{F}\right) \) - Three Single Canductors in Conduit


We have an Answer from Expert

View Expert Answer

Expert Answer


In this table , Effective impedance is defined as , where is the power factor of the circuit. Now , V = IR or IZ , so multiplying the current by e